WaveStar PowerPak PDU

WaveStar PowerPak PDU

PDI’s WaveStar® PowerPak PDU provides high distribution capacity and configuration flexibility:
• Up to (8) panelboards or (336) branch circuits
• Up to (12) subfeeds
• Monitoring available on all circuits
The PowerPak transformer is rated K-20, TP-1 compliant.

Power Monitoring
• Transformer input and output (standard)
• Branch Circuit Monitoring System for panelboards, main feeds to panelboards, and individual branch circuits.
• Interface board for HVAC contacts and building alarms
• WaveStar PDU monitoring
• Remote Communications Interface Modbus RTU or SNMP

Description

Electrical Characteristics

• Input 480VAC
• Output 208/120VAC
• 200% Neutral
• Square D main input breaker
• Single-Point Grounding
• Listed to UL Standard 60950

Distribution

• 225A secondary main breakers rated 22kAIC
• Square D NQOD panelboards
• Up to (2) panelboards in the standard unit
• Up to (8) panelboards with optional sidecars
• Up to (12) subfeeds (not all options can be installed simultaneously)

Enclosure

• Rigid split doors with 18″ swing
• Advanced door catch ensures positive closure
• Lexan viewing panel
• (4) stabilizer feet and casters

Transformer

• K-20, TP-1 compliant, 150⁰C, Class R insulation transformer
• (6) compensation taps
• 225 kVA and 300 kVA PDUs are TP-1 compliant with 5x inrush

Power Monitoring

• Transformer input and output (standard)
• Branch Circuit Monitoring System for panelboards, main feeds to panelboards, and individual branch circuits.
• Interface board for HVAC contacts and building alarms
• WaveStar PDU monitoring
• Remote Communications Interface Modbus RTU or SNMP

Other Features

• Local EPO
• Surface REPO pushbutton
• Transient Suppression
• Surge Suppression